From the picture below (on page 2), you will notice that the column named ‘Breaker Opening Time (sec.)’ has a white background. This means that it is an editable field in the arc flash spreadsheet.
There are two cases where you cannot change the breaker opening time in the arc flash evaluation:
1.) The fault current contribution is coming from an induction motor set within the Options menu to clear in a specified number of cycles.
2.) The maximum arcing duration has already been reached. Either because:
a. The protective device that is suppose to trip that portion of the arcing fault current is set above the maximum arcing duration.
b. You do not have a protective device to clear the arcing current.
|